Omron DRM21 module prompts E2 error, how to do?

plc automation electronic

Cause: indicates that the network communication timeout.

Countermeasures:

① Check the main station must use the same baud rate from the station;

② Check the wiring of communication cable is loose;

③ whether the two terminals of the network terminating resistor;

④ check the current speed and distance network, consider reducing the baud rate of the network, using 125Kbps baud rate for communication;

⑤ recommended DeviceNet dedicated cable network;

⑥ Whether there is signal interference around the communication apparatus.

 